Reduced Operational Costs at Plastic Factory
Case Studies » SinuMEC Case Studies » Reduced Operational Costs at Plastic Factory
CASE STUDY
|
|||||||||||||||||||||||||||||||||||||||||||||||
|
SinuMEC Mode
|
Bypass
|
Save
|
Saving
|
|
kW
|
5.02
|
4.26
|
15.1%
|
|
Amp
|
31.0
|
16.7
|
46.1%
|
|
PF
|
0.234
|
0.368
|
57.3%
|
|
kVAr
|
20.81
|
10.68
|
48.7%
|
|
kVA
|
21.45
|
11.56
|
46.1%
|
ELECTRICAL BENEFITS
The following direct benefits were achieved from the SinuMEC operation:
- Reduced direct kWh reading by 15%
- Reduced current and total power by 46%
- Reduced network & transformer losses by 71%
- Reduced reactive power by 49%, leading to reduced power factor capacitor demand and losses
- Increased motor and belt life expectancy
- Reduced startup current to 1.2 of nominal
- Reduced granulator down time
FINANCIAL BENEFITS
It was assumed that during its entire operating life time, the load operates at conditions similar to those during the test period.
Some savings cannot be measured without stopping loads and hence were only estimated. In order to verify correct estimation, a range of values was given (more details can be found in the article “Reducing Energy and Life Cycle Costs using Sinusoidal Motor Controllers” by S. Limor and A. Broshi).
The following table summarizes the different savings:
|
|
Min
|
Max
|
|
Direct power saving
|
0.76
|
0.76
|
|
Conduction losses
|
0.31
|
0.77
|
|
Transformer losses
|
0.31
|
0.77
|
|
Reduced PFC losses and harmonics pollution
|
0.10
|
1.03
|
|
Total kW
|
1.5
|
3.3
|
The motor is operated 24 hours a day, 7 days a week with a kWh price of €0.10 ($0.15). The total energy saving per year is 12,885 kWh to 29,070 kWh. With current electricity price this will save € 1,263 ($1,894) to € 2,849 ($4,273) per year with ROI of 11 to 24 months and IRR (Internal Rate of Return) of 59% to 123% on direct saving only. Since the company considered purchasing motor starter alone, when reducing the motor starter price, the ROI becomes 8 to 18 months only. As the electricity prices are constantly rising, ROI and RII times will be even shorter. In addition, this will increase the motor life expectancy and provide smooth motor startup. The environment will also benefit by reduction of 5,541 Kg to 12,500 Kg of CO2 emission.
When Eng. Gabriel Weiner, head of electrical department, who participated in the measurement process, noticed the results he said: “Great performance! Now I want SinuMEC on all my granulators.”
Similar benefits were measured in other SinuMEC installations in low or variable load motors, such as conveyors, sifters, compressors, escalators and mixers.